1、Introduction:
CP800 series UPS is 1 phase in and 1 phase out uninterruptible power supplies. It adopts advanced digital design and imported high performance IGBT&SCR, completely eliminates the interference from the electric networks, shows stable frequency, stable voltage, low distortion, low noise. The ideal applications are those places which are sensitive to power interference, and those need a stable, reliable, clean, continuous sine wave AC power supply. UPS internal circuits have CPU automatic detective management, high frequency IGBT invert, LCD display. It is widely used in telecom industry, office automation, personal computer, telecommunication, electric power, scientific research, medical treatment, bank.
2、Features:
Superior ability to adapt electric networks
220V±25% of wide input voltage range makes UPS work normally in poor power environment, it reduces the battery discharging opportunity and extends battery life.
Cold start
Battery pack can be activated directly by UPS in the absence of electric power, users' emergency needs can be fulfilled.
Super load compatibility
Strong carrying capacity, load compatibility, can be applied to different types of load, meet various application needs.
Perfect protection
Protection of input/output over-voltage, low-voltage, output over-current, short-circuit, battery low-voltage, battery over-charge, power device's over temperature, ensuring the stability of system.
No transfer time
Built-in static bypass electronic switch, if UPS is under protection or breakdown, the power supply will be switched to bypass without interruption. It especially suits equipments that have strict time requirements of power-fail.
Perfect battery management
Offer the most resonable charging current according to battery parameter curve, set the best charging current according to battery capacity, improve battery efficiency, extend battery lifespan.
High-current charger
Built-in high-current charger, can be applied to occasions with frequent power failures and long time power disconnection.
Large screen LCD+LED display, free human-machine communication.
UPS working state can be judged by LED, UPS parameters such as input/output and battery can be observed by LCD.
Intelligent monitoring function
Communicate with computer through RS232 interface and UPS intelligent monitoring software, display UPS working parameters on screen. UPS can also achieve network monitor through the installation of SNMP card, and can be observed and managed UPS working parameters remotely through the network.
Series connection hot backup and parallel connection redundancy can be achieved.
Parameters:
Model |
CP801 |
CP802 |
CP803 |
CP804 |
CP806 |
CP808 |
CP810 |
CP815 |
CP820 |
|||||||
Capacity |
1KVA |
2KVA |
3KVA |
4KVA |
6KVA |
8KVA |
10KVA |
15KVA |
20KVA |
|||||||
Operating principle |
Pure sine wave dual conversion on-line |
|||||||||||||||
AC input |
Phase |
single-phase L+N+G |
||||||||||||||
Voltage |
220V±25% |
|||||||||||||||
Frequency |
50HZ±10% |
|||||||||||||||
DC |
Rated DC voltage |
48Vdc |
192Vdc |
|||||||||||||
floating voltage |
54.5Vdc |
218Vdc |
||||||||||||||
Cut-off voltage |
42Vdc |
168Vdc |
||||||||||||||
Charging time |
charge to 90% in 8 hours |
|||||||||||||||
AC output |
Phase |
single-phase L、N+G |
||||||||||||||
Voltage |
220Vac±2%( stable load), 220Vac±5%(fluctuant load)) |
|||||||||||||||
Frequency |
50Hz±0.5%( On battery) |
|||||||||||||||
Power factor |
0.8 |
|||||||||||||||
Wave-form |
Sine wave |
|||||||||||||||
Total voltage harmonics distortion |
linear load <3%,non-linear load <5% |
|||||||||||||||
Output voltage transient characteristic |
±5%( Load abrupt change From 0 to 100%) |
|||||||||||||||
Transient response time |
<20ms |
|||||||||||||||
Crest factor |
3:1 |
|||||||||||||||
Overload protection |
>125%,1min;>150%,200ms |
|||||||||||||||
System spec |
Full load efficiency |
≥90% |
||||||||||||||
Transfer time |
0ms |
|||||||||||||||
Protection |
Overload, over charge and over discharge; out the range of voltage and frequency, over current, short circiut, over temperature ect. |
|||||||||||||||
Display |
LCD and LED indicator |
|||||||||||||||
Communication |
Rs232 interace and SNMP card(optional) |
|||||||||||||||
Environment temperature |
-5~40℃ |
|||||||||||||||
Relative ambient humidity |
20~95% (Non-condensing) |
|||||||||||||||
Altitude |
<1500m; 1% rated capacity decrease against rised 100m |
|||||||||||||||
Safety rate |
IP21 |
|||||||||||||||
Cooling method |
forced air-cooling with temperature control |
|||||||||||||||
Noise (dB) |
<55dB |
<60dB |
||||||||||||||
Dimension (W*D*H)mm |
200×480×490 |
210×612×540 |
240×540×680 |
330×640×885 |
380×681×935 |
|||||||||||
Weight (Kg) |
39 |
66 |
74 |
60 |
67 |
80 |
110 |
151 |
200 |
Copyright © 2012PageAdmin. All rights reserved. Zoomven Electric ICP number:粤ICP备06045717号